1. Home
  2. Data
  3. Bus Cables
  4. Echelon LonWork System Cabling - 22AWG

Echelon LonWork System Cabling - 22AWG

Designed for use on industrial and commercial bus systems, these cables have become increasingly popular on Building Management Systems (BMS). Available as one and two pair cables, screened and unscreened in Low Smoke Halogen Free compounds they provide the ideal low cost solution to BUS wiring.

Technical Information - Screened 

Voltage Rating:

Temperature
Rating:

Conductor
Resistance:


Velocity of
Propagation:

Capacitance:

Core to core:

Nominal
Impedance:

Colour Code:

300V

-5°C +60°C


53.0 Ω/km @ 20°C


55%


45pF/m @ 1kHz

100 Ohms

Black, white

Cable Contruction

Unscreened Pairs

22(1)AWG plain copper conductors, foam PE insulation, cores twisted into pairs,
Low Smoke Halogen Free sheath.

Technical Information - Unscreened 

Voltage Rating:

Temperature
Rating:

Conductor
Resistance:


Velocity of
Propagation:

Capacitance:

Core to core:

Nominal
Impedance:

Colour Code:

300V

-5°C +60°C


53.0 Ω/km @ 20°C


68%


45pF/m @ 1kHz

100 Ohms

Black, white

Cable Construction

Screened Pairs

22(1)AWG plain copper conductors, foam PE insulation, cores twisted into pairs, overall foil and 22(1)AWG TCu drain wire, Low Smoke Halogen Free sheath.

Hover Over Image to Enlarge
Print Product Datasheet
Part No.Alt. to BeldenNo. of PairsAWGSheath MaterialWeight Kg/KmO/D mmScreened
2201POFGH7703NH122(1)LSHF23.004.5CAT
2201PUGH7701NH122(1)LSHF14.003.5UNSCREENED
2202POFGH7704NH222(1)LSHF36.006.5CAT
2202PUGH7702NH222(1)LSHF27.005.0UNSCREENED

CAT - Collective Aluminium Tape