Used widely on ships, oil rigs, platforms and refineries where fire resistance to IEC 60331 is vital. BS 7917 cables provide circuit integrity to maintain essential services in the event of a fire.The 657M SW4 unarmoured versions are ideal for applications where small bending radii are required. When mechanical protection is needed the 658M SW4 steel braid armour (GSWB) version provides the solution whilst maintaining good flexibility for installation in restricted areas.
Voltage Rating:Conductor Stranding:Temperature Rating:Bending Radius Static:< 10mm2>10mm2 to 25mm2>25mm2Oxygen Index of Sheath:Fire Resistant:Flame Retardant:Smoke Emission:Halogen Emission:Manufactured To:
0.6/1kVIEC 60228 Class 2, tinned copper-30°C to +85°C
4 x cable OD4 x cable OD6 x cable OD>31%IEC 60331-21
IEC 60332-1-2, IEC 60332-3-22 Cat AIEC 61034-1 & 2, BS 7622IEC 60754-1 & 2, BS 6425-1BS 7917/BS 6883
Stranded tinned copper conductor, mica glass tape fire barrier, EPR insulation, halogen free thermoplastic elastomeric bedding, galvanized steel wire braid armour, SW4 LSHF elastomeric outer sheath - black.
White cores with black numbers. Colour coded cores available to order.
Flexible & Specialist Cables, Alban Point, Alban Park, Hatfield Road, St. Albans, Herts AL4 0JX