Audio/Visual/Data Cables
20AWG & 18AWG

Reduced losses are achieved through the use of 20AWG (0.56 mm²) or 18AWG (0.96mm²) conductors making this cable ideal for long runs. Widely used in monitoring, computer, instrumentation and audio applications where the individually screened pairs reduce cross talk.

2 Pair Construction 20AWG 0.56 mm²

Tinned copper conductor 20(7)AWG 0.56 mm², PVC insulated, twisted into pairs, each pair with aluminium/polyester foil screened, tinned copper drain wire (22AWG). Grey PVC sheath on standard cables. UL Style 2464 300V 80°C.
 

Multi-pair Construction 20AWG 0.56 mm²

Tinned copper conductor 20(7)AWG 0.56 mm², polyethylene insulated, colour chart 3. Twisted into pairs, each pair aluminium/polyester foil screened, tinned copper drain wire (22AWG), PVC sheath on standard cables. UL Style 2919 300V 80°C. Nominal Impedance 50 Ohms.

Multi-pair Construction 18AWG 0.96 mm²

Tinned copper conductor 18(16)AWG 0.96 mm², polyethylene insulated. Twisted into pairs, each pair aluminium/polyester foil screened, tinned copper drain wire (20AWG), PVC sheath on standard cables. UL Style 2919 300V 80°C. Nominal Impedance 50 Ohms.

Technical Data

Part No.
Belden
No.
No. of
Pairs
Weight
Kg/Km
O/D
mm
Capacitance
C/C
pF/m
C/S
Colour code

  20 AWG

  2002PIFY   9402   2   76   7.6   180   312   Blk/Red, Grn/Wht 
  2002PIFYH   LSHF   2   76   7.6   180   312   Blk/Red, Grn/Wht 
  2003PIFP   9873   3   104   8.4   98   180   Chart 3 
  2003PIFPH   LSHF   3   104   8.4   98   180   Chart 3 
  2006PIFP   9874   6   182   10.9   98   180   Chart 3 
  2009PIFP   9875   9   270   13.6   98   180   Chart 3 
  2011PIFP   9876   11   302   15.2   98   180    Chart 3  
  2012PIFP   9877   12   322   15.2   98   180   Chart 3 
  2015PIFP   9879   15   384   17.0   98   180   Chart 3 

  18 AWG

  1802PIFY   9368   2   103   9.6   187   335   ICEA E2 
  1802PIFPH   N/A   2   98   9.0   79   144   Blk/Red, Grn/Wht 
  1803PIFP   9773   3   139   10.3   98   180   Chart 3 
  1803PIFPH   LSHF   3   139   10.3   98   180   Chart 3 
Most sizes available from stock

UL style numbers are given for cross reference purposes only - not all the cables in this section are tested or approved by UL. If you require UL approved versions please tell us when you first enquire.

At FSC we refer to LSHF as Low Smoke Halogen Free

This term is interchangeable with LSZH (Low Smoke Zero Halogen), LSOH (Low Smoke Zero Halogen), OHLS (Zero Halogen Low Smoke) and FRNC (Flame Retardant Non-Corrosive). Beware of the terms LSF (Low Smoke and Fume) or RP (Reduced Propogation), when relating to signal or control cables will normally be modified PVC and produce 'Loads of Smoke and Fume'!

Fire retardant, fire resistant, flame resistant or flame retardant?

These terms are often misunderstood. Most cables when exposed to fire will not carry on functioning. If you require cable to continue working in the event of fire, and in accordance with various standards please call us.

 

 

 

 

 

 

 

 

 

 

 

 

 

Some common mispellings of Belden Cable include - Beldon, Beldan, Balden, Baldon and Beldin.

Back to last page Return to TOP