Shipwiring/Offshore Screened
Instrumentation Cables to BS6883
(Ref. 657 SW4 Instrumentation)

Manufactured in both pairs and triples these 150/250V instrumentation cables provide collective or individual screening through the use of metallic foils and drain wires. Offering good flexibility for installation in confined spaces or where difficult routing is necessary these cables are ideal where no additional mechanical protection is required.

Using the latest SW4 Low Smoke Halogen Free sheathing compounds ensures that in the event of a fire the cables offer excellent protection to both people and property by not emitting toxic or corrosive gases.

  

Cable Construction -
Individually screened

Tinned copper wire conductors to BS 6360, class 2 or class 5, EPR insulation, cores twisted into pairs or triples, each pair foil screened with a drain wire, SW4 LSHF sheath - grey or blue.

Cable Construction -
Collectively screened

Tinned copper wire conductors to BS 6360, class 2 or class 5, EPR insulation, cores twisted into pairs or triples, overall foil screen and drain wire, SW4 LSHF sheath - grey or blue.

Core Identification

Pairs : Each pair black, white and numbered
Triples :   Each triple black, white, red and numbered
(Alternative colour codes are available)

Technical Information

Voltage rating 150/250V
Conductors Tinned, BS6360 class 2 or class 5
Temperature rating +90°C maximum conductor temperature
Static temperature rating -30°C to +90°C
Bending radius (static) 8 x cable O/D
Flame retardant IEC60332 part 3A, BS4066 part 3A
   
Fire resistant versions to IEC60331 are also available, ref BS7917

Technical Data - CMA Ref 657 SW4 Instrumentation to BS6883

Part No.
No. of
Pairs
Nominal Conductor
Cross-Sectional
Area mm²
Nominal Diameter
of Cable
Min-Max mm

 Pairs collective

 657C0703PxxH   3   0.75   12.6 - 14.5 
 657C0707PxxH   7   0.75   16.6 - 18.7 
 657C0712PxxH   12   0.75   21.7 - 24.2 
 657C0720PxxH   20   0.75   27.3 - 30.1 
 657C0727PxxH   27   0.75   31.1 - 34.2 
 657C0737PxxH   37   0.75   34.4 - 37.7 
              
 657C1003PxxH   3   1   13.3 - 15.3 
 657C1007PxxH   7   1   17.6 - 19.8 
 657C1012PxxH   12   1   23.1 - 25.7 
 657C1020PxxH   20   1   29.1 - 31.9 
 657C1027PxxH   27   1   33.3 - 36.6 
 657C1037PxxH   37   1   36.9 - 40.3 

 Pairs individual

 657I0701PxxH   1   0.75   7.3 - 9.0 
 657I0703PxxH   3   0.75   12.6 - 14.5 
 657I0707PxxH   7   0.75   16.9 - 19.0 
 657I0712PxxH   12   0.75   21.2 - 23.7 
 657I0720PxxH   20   0.75   27.0 - 29.8 
 657I0727PxxH   27   0.75   30.8 - 33.9 
 657I0737PxxH   37   0.75   35.9 - 39.3 
              
 657I1001PxxH   1   1   7.7 - 9.5 
 657I1003PxxH   3   1   13.5 - 15.5 
 657I1007PxxH   7   1   18.0 - 20.1 
 657I1012PxxH   12   1   22.8 - 25.4 
 657I1020PxxH   20   1   28.8 - 31.6 
 657I1027PxxH   27   1   32.8 - 36.0 
 657I1037PxxH   37   1   38.5 - 42.3 
Part No.
No. of
Triples
Nominal Conductor
Cross-Sectional
Area mm²
Diameter over
outer sheath
min-max mm

 Triples collective

 657C0703TxxH   3   0.75   14.2 - 16.2 
 657C0707TxxH   7   0.75   19.4 - 21.9 
 657C0712TxxH   12   0.75   24.2 - 26.8 
           
 657C1003TxxH   3   1   15.1 - 17.1 
 657C1007TxxH   7   1   20.9 - 23.4 
 657C1012TxxH   12   1   25.8 - 28.5 

 Triples individual

 657I0701TxxH   1   0.75   7.7 - 9.4 
 657I0703TxxH   3   0.75   14.2 - 16.2 
 657I0707TxxH   7   0.75   19.7 - 22.1 
 657I0712TxxH   12   0.75   24.4 - 27.1 
           
 657I1001TxxH   1   1   8.4 - 10.1 
 657I1003TxxH   3   1   15.0 - 17.2 
 657I1007TxxH   7   1   21.0 - 23.5 
 657I1012TxxH   12   1   26.2 - 28.9 
"xx" TO SHOW THE COLOUR PLEASE REPLACE "xx" WITH
 - 05 FOR GREY
 - 01 FOR BLUE

At FSC we refer to LSHF as Low Smoke Halogen Free

This term is interchangeable with LSZH (Low Smoke Zero Halogen), LSOH (Low Smoke Zero Halogen), OHLS (Zero Halogen Low Smoke) and FRNC (Flame Retardant Non-Corrosive). Beware of the terms LSF (Low Smoke and Fume) or RP (Reduced Propogation), when relating to signal or control cables will normally be modified PVC and produce 'Loads of Smoke and Fume'!

Fire retardant, fire resistant, flame resistant or flame retardant?

These terms are often misunderstood. Most cables when exposed to fire will not carry on functioning. If you require cable to continue working in the event of fire, and in accordance with various standards please call us.